JGS flanged immersion heater bundle rated 3 to 45 kW at 380 V or 220 V
Resistencia de inmersión JGS para calderas y agua
JGS 型锅炉用管状电热元件
Conjunto de inmersión para agua de alimentación de caldera y agua caliente en recirculación hasta 160 °C. Tubo de acero 20#, 304, 316 o 316L, suministrado como haz con brida o como elemento roscado individual.
- Max medium temperature
- 320 °F(160 °C)
- Power range
- 1 – 45 kW
- Voltage
- 220 / 380 V, 50 Hz
- Sheath material
- 20# steel, 304 stainless, 316 stainless, 316L stainless
- Medium
- Water, Steam
- Mounting
- Flange, Threaded boss
- Tube diameter
- 0.472–0.63 in
- Pressure rating
- 116–580 psi
- Lead time
- 18–30 days
- MOQ
- 5 units
- Pricing
- On application
Design notes
Montaje con brida o rosca, sellado para 0,8–4 MPa
JGS assemblies heat water inside a pressure vessel — a hot-water boiler, a calorifier, a buffer tank or a steam generator shell. The heated element is the same tubular construction used across the range; what changes is the pressure boundary. A machined flange with a gasket face, or a threaded boss with a sealing washer, carries the seal and the assembly is hydro-tested before dispatch.
Material choice follows water chemistry rather than temperature. 20# carbon steel is adequate for closed, chemically treated circuits where oxygen is scavenged and make-up is minimal. Open circuits, softened water, and anything with meaningful chloride content should go to 304, and 316 or 316L where chlorides are high — a stainless immersion heater in the wrong grade pits along the waterline faster than carbon steel would.
The other design decision is scale. Hard water deposits carbonate on the sheath, and like carbon in oil it insulates: the element runs hotter under the deposit until the coil fails. In hard-water regions specify a lower watt density and plan for descaling access, or feed the vessel through a softener.
Features
- Instalación sellada calificada para 0,8–4 MPa
- Vaina de acero 20#, 304, 316 o 316L según la química del agua
- Haces con brida o elementos roscados individuales
- Conjuntos de 3 kW a 45 kW a 220 V o 380 V, 50 Hz
- Probados hidrostáticamente y con megóhmetro antes del despacho
Typical applications
- Calderas eléctricas de agua caliente e interacumuladores
- Cuerpos de generadores de vapor
- Calentamiento de agua de proceso y tanques CIP
- Calentamiento de apoyo en redes y tanques de amortiguación
- Protección contra congelamiento en recipientes a la intemperie
North American build options
- Voltage
- 120 / 208 / 240 / 277 / 480 / 600 V @ 60 Hz
- Threads
- NPT or BSP cut to order
- Flanges
- ANSI B16.5 150# / 300#
- Drawings
- Issued in inches on request
These are build options, not stock items — the catalog part numbers above are 50 Hz with metric fine threads. State what you need on the RFQ.
Part numbers & dimensions
13 catalog part numbers in the JGS series
Bundle assemblies are configured per order: flange standard and size, element count, sheath grade, terminal enclosure and thermostat pocket are all set at drawing approval. Send your flange detail with the inquiry.
Minimum order quantity for this series is 5 units. Dimensions switch between millimetres and inches with the unit toggle in the header.
Full specification
- Sheath material
- 20# steel, 304, 316 or 316L stainless
- Max. water temperature
- 160 °C
- Sealed pressure rating
- 0.8 – 4 MPa
- Mounting
- Machined flange or threaded fastening boss
- Assembly power
- 3 – 45 kW typical bundle
- Voltage
- 220 V or 380 V, 50 Hz
- Terminal seal
- Silicone with optional IP54 terminal box
- Insulation resistance
- ≥ 1 MΩ at 500 V DC
- Standard
- JB/T 2379-93
Questions engineers ask
Do I need stainless steel, or will carbon steel do?
It depends on the water, not the temperature. Closed, chemically treated circuits with scavenged oxygen and little make-up run fine on 20# carbon steel. Open circuits, softened water and anything carrying chloride should be 304, moving to 316 or 316L as chloride rises. Getting this wrong shows up as pitting along the waterline within months.
How does hard water shorten element life?
Calcium carbonate deposits on the sheath and insulates it. Heat that used to leave into the water is now trapped, so the coil temperature climbs under the scale until it fails — the element is destroyed by its own output. In hard-water areas specify a lower watt density, leave descaling access, or soften the feed.
What pressure rating can you seal to?
Standard flange and threaded builds seal from 0.8 to 4 MPa, and every assembly is hydro-tested before dispatch. Send us the vessel's design pressure and the flange standard you work to — DIN, ANSI, JIS or GB — and we will match the mating face rather than supplying a flange you then have to adapt.
Can you fit a thermostat or thermowell into the assembly?
Yes. A thermowell in the flange face, a capillary thermostat pocket, or a bulb well positioned in the bundle are all standard options. Say what control device you intend to use and we will place the pocket where it reads the water rather than the sheath — a common installation error that makes control hunt.
Commonly specified with
Related series
JGGSegún planoGenerador de vapor eléctrico
Unidades empaquetadas de 3 a 45 kW a 220 V o 380 V, 50 Hz
- Temp. máx.
- 356 °F
- Potencia
- 3–45 kW
- Núm. de parte
- 10
JGBSegún planoResistencia de inmersión antideflagrante con brida
Caja antideflagrante, flujo deflectado, límite alto independiente
- Temp. máx.
- 842 °F
- Potencia
- 3–200 kW
- Núm. de parte
- 8
JGYSegún planoElemento de inmersión en aceite JGY
Tanques de aceite abiertos y cerrados, 1–8 kW a 220 V
- Temp. máx.
- 572 °F
- Potencia
- 1–8 kW
- Núm. de parte
- 11